207
Binary input: ForceValueIn 1
Related FW
3.0
Description
This input activates the Force value #1 block. If the input is active, the value of the
setpoint, to which the Force value #1 block is configured, will be overriden by value
of the alternative setpoint assigned to the Force value #1 block.
NOTE:
If there are more than one force value blocks configured onto one setpoint then the
highest priority has the block with the lowest index (i.e. the first active block
according to the list displayed in GenConfig in the Force value window at the related
setpoint).
NOTE:
Watch a training video about force value function here:
http://www.comap.cz/support/training/training-videos/.
EXAMPLE OF AN ACTIVE FORCE VALUE BLOCK