This setpoint adjusts the delay after the binary input Force block 3 has been
deactivated, when the alarms configured as Force block #3 are started to be
evaluated.
Pressing of the fault reset button (at any terminal or external
button) resets only inactive alarms. Active alarms remain in
the alarmlist unchanged and must be reset again when they
become inactive.
Pressing of the fault reset button (at any terminal or external
button) resets all alarms that are currently present in the alarm
list. Inactive alarms disappear from the alarm list immediately,
active alarms are changed to "confirmed" state and disappear
when the alarm condition disappear or the alarm starts to be
blocked.
NOTE:
ENABLED position corresponds to the method how the IG-classic and IS-classic
controllers handled the alarms.
Group: Analog protect
Setpoint: Batt >V
This setpoint adjusts the warning level for battery overvoltage alarm.
This setpoint adjusts the warning level for battery undervoltage alarm.