Inteli NT GeCon MINT, SW Version 1.4, ©ComAp – June 2007
IGS-NT-GeCon-MINT-1.4.PDF
13
switch-off automatically in one or more controllers if there is not enough load to cover all the requested
LocalBaseloads.
Important setpoints: ProcessControl: LocalBaseload.
System Base power factor
Gen-set group is controlled in mains parallel to keep a constant (or adjustable) power factor.
Important setpoints: ProcessControl: #SysPFCtrlPtM = BASEPF; #SysPwrFactor.
Import-Export
Gen-set group is controlled to keep constant (or adjustable) Import or Export value. The external controller
InteliMains NT must be connected on the CAN2 to control gen-set group kW I/E.
Important setpoints: ProcessControl: #SysLdCtrlPtM = LDSHARING.
Import/Export power factor
Gen-set group is controlled to keep constant (or adjustable) Import or Export power factor.
Important setpoints: ProcessControl: #SysLdCtrlPtM = VSHARING. The external InteliMains NT controller
must be connected on the CAN2 to control gen-set group PF I/E.
Service time alarm
Engine starting procedures
• Independent Engine controller (e.g. InteliDrive) is expected.
• Interface GeCon to InteliDrive is provided by single BI/BO wires (no communication line).
• GeCon does not directly control engine via Starter, Fuel, Ignition – only sends Start request and Stop
requests.
• Automatic engine start/stop is allowed in GeCon - AUT mode when Power management function is
active.
• GeCon does not measure RPM from pickup.
Engine stopping procedures
• Active Generator protection does not stop running engine (except Power management in AUT mode).
• Engine stop command from MCU opens GCB (via BO Ready to load without Unloading).
Engine “running” conditions
• The additional condition to close GCB (start synchronizing) is GeCon BI Ready to load (coming from
MCU) in both MAN, AUT modes.