Inteli NT GeCon MINT, SW Version 1.4, ©ComAp – June 2007
IGS-NT-GeCon-MINT-1.4.PDF
12
Load reconnection – automatic -> AutoLd recon = ENABLED
Ld recon del Ld recon delLd recon del
BO Load shed 2
Ld recon level
Gen-set power
BO Load shed 3
BO Load shed 1
opened
opened
opened
Load reconnection – manual -> AutoLd recon = DISABLED
System Base load
Gen-set group is controlled on constant (or adjustable) power. The Baseload value can by changed by
setpoint or via analog input.
Important setpoints: ProcessControl: #SysLdCtrlPtM = BASELOAD; #SysBaseload; SysBaseLdMode.
Local Baseload
Selected gen-set from island or mains parallel running group can be loaded to constant LocalBaseload
value. This engine is taken out from Load sharing and Power management. LocalBaseload value is reduced
only when common group (actual) load is lower than this value.
The gen-sets in the group will try to match their LocalBaseloads (when more than one) based on their
controller addresses, so the first limited would be the one with the highest CAN address. I.e. this function will

Questions and Answers: