EasyManua.ls Logo

ComAp IG-NTC - Binary Inputs - Status Information

ComAp IG-NTC
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Inteli NT GeCon MINT, SW Version 1.4, ©ComAp – June 2007
IGS-NT-GeCon-MINT-1.4.PDF
23
Hint:
Pulse width (both high/low levels) must be at least 100 ms in order to be correctly sensed!
Conversion ratio can be selected using the setpoints ConvCoefPulseX. The converted values are visible in
statistics – values PulseCounter X. These values can be reset using Statistics window in InteliMonitor.
Timer block 1 … 16
Sixteen blocking inputs for particular timer module channels. The input can lock out its assigned channel – if
this input is active, the channel won’t activate its output (Timer active X) to e.g. start the engine.
Lang sel int A … Lang sel int C
Set of binary inputs for forcing alternative languages. This set of inputs is switching the controller’s internal
terminal – for IG-based controllers the front panel, for IS-based controllers the IS-Display with address #1.
Encoding of binary inputs’ combinations:
Language index -> given by display setting 1 2 3 4 5 6 7
Lang sel int A 0 1 0 1 0 1 0 1
Lang sel int B 0 0 1 1 0 0 1 1
Lang sel int C 0 0 0 0 1 1 1 1
Hint:
Warning – each language change causes the restart of the respective display (not the whole controller), so
the display’s control panel won’t react until the restart has finished (~ 5s).
Value 0 in the table denotes that the corresponding input is not active or not configured.
If more than 7 languages are present in the controller, it is not possible to force languages with index higher
than 7 using these binary inputs.
The reaction on BI combination change is 1s delayed not to react on transient combinations if a rotary
selector switch is used.
Lang sel D#2 A
Lang sel D#2 B
Lang sel D#2 C
Set of binary inputs for forcing alternative languages. This set of inputs is switching the controller’s external
terminal with address #2 – for IG-based controllers the IG-Display, for IS-based controllers the IS-Display
with address #2.
Encoding of binary inputs’ combinations:
Language index -> given by display setting 1 2 3 4 5 6 7
Lang sel D#2 A 0 1 0 1 0 1 0 1
Lang sel D#2 B 0 0 1 1 0 0 1 1
Lang sel D#2 C 0 0 0 0 1 1 1 1
Hint:
Warning – each language change causes the restart of the respective display (not the whole controller), so
the display’s control panel won’t react until the restart has finished (~ 5s).
Value 0 in the table denotes that the corresponding input is not active or not configured.
If more than 7 languages are present in the controller, it is not possible to force languages with index higher
than 7 using these binary inputs.
The reaction on BI combination change is 1s delayed not to react on transient combinations if a rotary
selector switch is used.
Lang sel D#3 A
Lang sel D#3 B
Lang sel D#3 C
Set of binary inputs for forcing alternative languages. This set of inputs is switching the IS-Display with
address #3.

Related product manuals