Inteli NT GeCon MINT, SW Version 1.4, ©ComAp – June 2007
IGS-NT-GeCon-MINT-1.4.PDF
36
Recommended wiring:
Without InteliMains With InteliMains
Derating1 strt [ X ] (FV)
Derating2 strt [ X ] (FV)
The starting values for the power derating function. The gen-set nominal power is decreased according to
the adjusted curve.
The setpoint actual physical dimension is given by the related analog input and the value assigned to it.
Step: 1 X
Range: ± 32000 X
Force value possibility: Yes
Hint:
DeratingX strt unit [X] depends on DeratingPowerX analog input unit. It can be e.g.°C in case of temperature
derating function.
Derating1 end [ X ] (FV)
Derating2 end [ X ] (FV)
Ending value for power limitation – at this value the gen-set power is limited to DeratingX pwr value and it
won’t go lower for higher input values.
The setpoint actual physical dimension is given by the related analog input and the value assigned to it.
Step: 1 X
Range: ± 32000 X
Force value possibility: Yes
Hint:
To record the power derating activity into the History: