Inteli NT GeCon MINT, SW Version 1.4, ©ComAp – June 2007
IGS-NT-GeCon-MINT-1.4.PDF
44
Force value: Yes
RunOnlyBlkDel1 [ s ]
Delay for Engine running Alarms activation – group 1 – see drawing below.
Step: 0,1s
Range: 0,0 – 3000,0 s
RunOnlyBlkDel2 [ s ]
Delay for Engine running Alarms activation – group 2.
Step: 0,1s
Range: 0,0 – 3000,0 s
RunOnlyBlkDel3 [ s ] (FV)
Delay for Engine running Alarms activation – group 3.
Step: 0,1s
Range: 0,0 – 3000,0 s
Force value: Yes
BINARY INPUT
BinInp delayX
physical
closed
Engine running
state
RunOnlyBlkDel
PROTECTION
active
inactive
Hint:
Engine running state = RPM > Engine params: Starting RPM or
Analog input Oil pressure > Engine params: Starting POil or
Active Binary input Run indication1 or
Active Binary input Run indication2 or
Active Binary input Run indication3.
BinInp delay 1 [ s ] (FV)
Binary input protection is activated when input is closed for longer time than BinInp delay 1. To use this
delay, Binary input must be configured in GenConfig for Property – Delay = BinInp delay 1.
Step: 0,1s
Range: 0,0 – 600,0 s
Force value: Yes
BinInp delay 2 [ s ] (FV)
Binary input protection is activated when input is closed for longer time than BinInp delay 2. To use this delay
Binary input must be configured in GenConfig for Property – Delay = BinInp delay 2.
Step: 0,1s
Range: 0,0 – 600,0 s
Force value: Yes