InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
115
12.2.2.13 Setpoint: AuxCurrCTprim
Group
Basic settings
Range [units]
1 .. 15000 [A]
Related FW
3.0
Description
Auxiliaries Current Transformer ratio primary side.
12.2.2.14 Setpoint: AuxCurrCTsec
Group
Basic settings
Range [units]
/1A, /5A [A]
Related FW
3.0
Description
Auxiliaries Current Transformer ratio secondary side.
NOTE:
Restricted to selection of /5A or /1A.
12.2.2.15 Setpoint: FixVoltProtSelect
Group
Basic settings
Range [units]
PHASE-NEUTRAL, PHASE-PHASE [-]
Related FW
3.0
Description
PHASE-NEUTRAL
The busL/busR voltage protections are based on
phase-to-neutral voltages.
PHASE-PHASE
The busL/busR voltage protections are based on
phase-to-phase voltages.
12.2.2.16 Setpoint: Nominal Freq
Group
Basic Settings
Range [units]
50 Hz, 60 Hz [-]
Related FW
3.0