This setpoint adjusts the warning level for battery overvoltage alarm.
12.2.5.2 Setpoint: Batt <V
Group
Analog protect
Range [units]
8.0 .. 40.0 [V]
Related FW
3.0
Description
This setpoint adjusts the warning level for battery undervoltage alarm.
12.2.5.3 Setpoint: Batt volt del
Group
Analog protect
Range [units]
0 .. 600 [s]
Related FW
3.0
Description
This setpoint adjusts the delay for battery overvoltage and undervoltage
alarms.
12.2.6 Group: BusL protect
12.2.6.1 Setpoint: BusL2POvrldPro
Group
BusL protect
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Force value
possible
YES
Description
Enables or disables the busL overload (IDMT) protection. This protection is
evaluated with variable delay. For more information see setpoint
2POvrldStEvDel.