InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
189
possible
Description
This setpoint adjusts the reset (initial) value of the ExtValue 2. This initial
value is applied either when the controller is powered-on or when the
ExtValue 2 is reset by the binary input ExtValue2reset.
12.2.11.31 Setpoint: ExtValue3deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the reset (initial) value of the ExtValue 3. This initial
value is applied either when the controller is powered-on or when the
ExtValue 3 is reset by the binary input ExtValue3reset.
12.2.11.32 Setpoint: ExtValue4deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the reset (initial) value of the ExtValue 4. This initial
value is applied either when the controller is powered-on or when the
ExtValue 4 is reset by the binary input ExtValue4reset.
12.2.12 Group: Load shedding
12.2.12.1 Setpoint: Ld shed level
Group
Load shedding
Range [units]
Ld recon level .. 200 [%]
Related FW
3.0
Force value
YES