EasyManua.ls Logo

ComAp IM-NT-BB - Page 269

ComAp IM-NT-BB
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
269
14.2.1.54 Binary input: ExtValue4 down
Related FW
3.0
Description
While this input is active the value of ExtValue 4 is contiously beeing
decreased at the rate of ExtValue4 rate until it reaches ExtValue4LoLim.
NOTE:
If this input is used (configured), the ExtValue 4 can't be written remotely
from a remote terminal using the command ExtValue 4.
14.2.1.55 Binary input: ExtValue1reset
Related FW
3.0
Description
The ExtValue 1 is reset to it's default value when this input is activated and
held there until the input is deactivated. The default value is given by the
setpoint ExtValue1deflt.
While the reset input is active:
The value does not respond to up and down inputs.
The value does not accept new data that are written remotely from a
remote terminal using the ExtValue command.
NOTE:
Configuring of the reset input does not block writing the ExtValue remotely, in
comparison to the up and down inputs, which does. However, if the reset
input is active, the remotely written data are not accepted.
14.2.1.56 Binary input: ExtValue2reset
Related FW
3.0
Description
The ExtValue 2 is reset to it's default value when this input is activated and
held there until the input is deactivated. The default value is given by the
setpoint ExtValue2deflt.
While the reset input is active:
The value does not respond to up and down inputs.
The value does not accept new data that are written remotely from a
remote terminal using the ExtValue command.
NOTE:
Configuring of the reset input does not block writing the ExtValue remotely, in

Table of Contents