InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
169
The combinations of gensets must be created so, that the total nominal
power of the Power band #1 < #2 < #3 < #4.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.33 Setpoint: #PwrBandContr 4
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power
band #4 if the optimalization according to gen-set size is active. Learn more
about this topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal
power of the Power band #1 < #2 < #3 < #4.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.34 Setpoint: #PwrBnChngDlUp
Group
Pwr management
Range [units]
0 .. 3600 [s]
Related FW
3.0
Description
This setpoint is used for adjusting the delay of changing the power band if the
load demand rose above the upper limit of the current power band. Learn
more about this topis in the chapter Gen-set size optimalization.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.