InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
171
possible
Description
This setpoint adjusts maximum difference between busL and busR voltage in
respective phases for voltage matching during synchronizing.
12.2.9.2 Setpoint: BRtoBLAngleReq
Group
Sync ctrl
Range [units]
-45 .. 45 [°]
Related FW
3.0
Description
Requested phase difference between busR and busL voltage during
synchronizing. Use this setpoint for phase correction of potential transformers
connection.
EXAMPLE:
Bellow there is an example of the controller connection to a high voltage
system.
T1 shifts phase +30° and no shift is on T2.
BtoM AngleReq = +30° needs to be set for this example.
12.2.9.3 Setpoint: Phase window
Group
Sync ctrl
Range [units]
0 .. 90 [°]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts maximum absolute value of difference between actual
phase angle between the busR and busL voltages for synchronizing.
NOTE: