InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
228
13.1.5.5 Value: Reserve Stp
Group
Pwr management
Units
kX
Related FW
3.0
Description
Actual absolute reserve - when the reserve is higher than this value the last
started gen-set (the gen-set with the highest priority) is stopped. This value
contains the following: #LoadResStop plus Nominal power of the genset
which is first to stop. #LoadResStop is used from the currently selected
reserve set.
13.1.5.6 Value: ActRes rel
Group
Power management
Units
%
Related FW
3.0
Description
Actual relative reserve. This value is active only when BTB is closed.
13.1.5.7 Value: ResStart rel
Group
Power management
Units
%
Related FW
3.0
Description
If the actual relative reserve is lower than this value the next gen-set which is
about to be started in power managament is started. This value is the exact
copy of setpoint #%LdResStrt X.
13.1.5.8 Value: ResStp rel
Group
Power management
Units
%
Relate
d FW
3.0
Descri
ption
Actual relative reserve - when the relative reserve is higher than this value the last started
gen-set (the gen-set with the highest priority) is stopped. This value contains the following: