EasyManua.ls Logo

ComAp IM-NT-BB - Page 244

ComAp IM-NT-BB
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
244
Related FW
3.0
Description
This value contains date of next activation of the timer block 13-16 (i.e. of the
output TimerAct 13-16). The related time is available in the value
NextTime13-16.
NOTE:
More information about timers is available in the chapter General purpose
timers.
13.1.12.23 Value: AirGate ID
Group
Info
Units
-
Related FW
3.0
Description
If the controller is connected to an AirGate server this value displays the ID
string assigned by the server. This ID string is to be used in ComAp PC tools
(e.g. InteliMonitor) to specify the respective controller when the connection is
opened.
13.1.12.24 Value: AirGate status
Group
Info
Units
-
Related FW
3.0
Description
This value displays actual status of the connection to the AirGate server.
0
Not connected to AirGate.
1
Connected, registered, waiting for autorization.
2
Registration denied.
3
Can not register, no free capacity in the server.
4
Can not register, other reason.
5
Connected, registered, authorized.

Table of Contents