channel #1. Type of the channel is to be adjusted by the setpoint AcallCH1-
Type.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
1. Select a binary signal in the controller, which indicates, that the
particular situation occured, about which you want to be informed
remotely. There are many predefined binary informations provided
directly by the controller or use PLC functions to create the desired
binary signal.
2. Configure an universal protection block to the binary signal
mentioned above and select protection type AL indication.
3. Configure the binary signal mentioned above onto the logical binary
input IssueActCallC1.
14.2.1.60 Binary input: IssueActCallC2
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the
channel #2. Type of the channel is to be adjusted by the setpoint AcallCH2-
Type.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
1. Select a binary signal in the controller, which indicates, that the
particular situation occured, about which you want to be informed
remotely. There are many predefined binary informations provided
directly by the controller or use PLC functions to create the desired
binary signal.
2. Configure an universal protection block to the binary signal
mentioned above and select protection type AL indication.
3. Configure the binary signal mentioned above onto the logical binary
input IssueActCallC2.
14.2.1.61 Binary input: IssueActCallC3
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the
channel #3. Type of the channel is to be adjusted by the setpoint AcallCH3-
Type.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
1. Select a binary signal in the controller, which indicates, that the
particular situation occured, about which you want to be informed
remotely. There are many predefined binary informations provided
directly by the controller or use PLC functions to create the desired