InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
307
15.2.1.60 Binary output: CtrlHBeat FD
Related FW
3.0
Description
This output is used at a redundant controller to disconnect the main
controller, connect the redundant one instead and activate it.
The output is closed:
If the input CtrlHBeat sens is configured onto any input terminal and
the redundancy controller does not sense the "heart beat" signal from
the main controller at that terminal.
If the redundant controller has not received two consequent
messages from the main controller. The address of the main
controller for the particular redundant one is selected by the the
setpoint Watched Contr
.
NOTE:
Learn more about redundancy in separate chapter Redundant controllers.
15.2.1.61 Binary output: Engines swapped
Related FW
3.0
Description
This output is activated by the master controller for 100 ms pulse when the
priority of two gen-sets was swapped by the Running hours equalization
function.
15.2.1.62 Binary output: Logical 0
Related FW
3.0
Description
This output is always opened. It may be used in functions (e.g. ECU outputs
or PLC modules inputs) where a binary value is required, however it has to
be continously inactive.
15.2.1.63 Binary output: Logical 1
Related FW
3.0
Description
This output is always closed. It may be used in functions (e.g. ECU outputs
or PLC modules inputs) where continuously active binary value is required.