EasyManuals Logo

ComAp InteliLite MRS16 Global Guide

ComAp InteliLite MRS16
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #239 background imageLoading...
Page #239 background image
InteliLite Global Guide
239
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15672 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Overspeed protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoint Overspeed Sd
(page 207).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 534).
Overspeed Protection
6 back to List of setpoints
Group: Dual Operation
Subgroup: Dual Operation
Setpoint group Dual Operation Related FW 1.9.0
Range [units] 0,1 .. 1000,0 [h]
Default value 10 h Alternative config NO
Step 0,1 h
Comm object 16039 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
343) and COM2 Mode (page 345)
Description
This setpoint adjusts the maximal allowed difference of dual operation running hours between Master and
Slave. When difference is higher, swap of load between controllers should be done.
Running Hours Max Difference
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals