EasyManua.ls Logo

ComAp intelilite nt amf25

ComAp intelilite nt amf25
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 135
IL-NT-AMF-2.2-Reference Guide.pdf
RxD 2
3 TxD
TxD 3
2 RxD
GND 5
5 GND
Remote RS485 and/or direct RS232 connection
HW module:
IL-NT-RS232-485
Up to 1000 meters (only with RS485):
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display Master controller
RS 232 (COM1)
OR
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display Master controller
RS 485 (COM2)
OR
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display 1 Master controller
RS 485 (COM2)
IL-NT
ID-Lite
IL-NT-
RS232-485
Remote Display 2
RS 232 (COM1)
Case 1) RS232
Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
Case 2) RS485
Master controller settings:
ControllerAddr = 1..32
COM2 Mode = DIRECT

Table of Contents

Related product manuals