InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 135
IL-NT-AMF-2.2-Reference Guide.pdf
RxD 2
3 TxD
TxD 3
2 RxD
GND 5
5 GND
Remote RS485 and/or direct RS232 connection
HW module:
IL-NT-RS232-485
Up to 1000 meters (only with RS485):
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display Master controller
RS 232 (COM1)
OR
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display Master controller
RS 485 (COM2)
OR
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display 1 Master controller
RS 485 (COM2)
IL-NT
ID-Lite
IL-NT-
RS232-485
Remote Display 2
RS 232 (COM1)
Case 1) RS232
Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
Case 2) RS485
Master controller settings:
ControllerAddr = 1..32
COM2 Mode = DIRECT