EasyManua.ls Logo

ComAp intelilite nt amf25

ComAp intelilite nt amf25
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 34
IL-NT-AMF-2.2-Reference Guide.pdf
Magnetic pick-up
To ensure proper function:
Use a shielded cable
Be aware of interference signal from Speed governor when one speed pick-up is used.
If engine will not start:
- Check ground connection from pick-up to controllers, eventually disconnect ground connection
to one of them
- Galvanically separate InteliLite RPM input using ComAp separation transformer RPM-ISO
(1:1)
- Use separate pick-up for Speed governor and InteliLite
NT
Hint:
In some cases the controller will measure a RPM value even though the gen-set is not running:
RPM is measured from the generator voltage (Gear Teeth = 0)
IL-NT is measuring some voltage value on input terminals due to open fusing.
If RPM > 0 the controller will be put into a Not ready state and the engine will not be allowed to start.
Current measurement
The number of CT’s is automatically selected based on selected value of setpoint ConnectionType
[3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph].
Hint:
Further information about measurement limits are at setpoint CT Ratio [/5A] description in chapter
Setpoints - Basic Settings.
Generator currents and power measurement is suppressed if current level is bellow <1% of CT
range.
To ensure proper function:
Use cables of 2,5mm
2
Use transformers to 5A
Connect CT according to following drawings:
Three phase application:
+
Battery
-
iL
GAC
Speed Control Unit
ESD 5500
MAGNETIC
PICK-UP
C
D
a
b
Signal
Signal
+
+-
-
Power
Supply
Power
Supply

Table of Contents

Related product manuals