14 Changes in the version 1.1.1
14.1 Support of direct communication between
InteliVision 5 and IG/IS-NT-(BB) controllers
It enables the usage of converters with constant communication speed in both directions between
InteliVision 5 and the controller.
With version 1.1.1 it is possible to run InteliVision 5 connected to controller RS232 or RS485 port with
following setting in the controller:
Option Controller port Setting in the controller
A RS232(1)
RS232(1) mode = DIRECT
RS485(1)conv. = DISABLED
B RS485(1)
Not possible
Port dedicated to NT-terminal line connection
C RS232(2)* **
RS232(2) mode = DIRECT
RS485(2)conv. = DISABLED
D RS485(2)*
RS232(2) mode = DIRECT
RS485(2)conv. = ENABLED
* RS232 OR RS485 direct connection can be used. They cannot be used simultaneously.
** Only available in IG-NTC / IS-NT-BB
IMPORTANT: It is not possible to program InteliVision 5 through the direct communication
interface. Programming, font upgrade and download of the logo have to be done through NT-
terminal line (connection of InteliVision 5 to RS485(1) port dedicated to displays).