IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
ALARM GROUPS ACCORDING TO BLOCKING TYPE
Setpoint: RunOnlyBlkDel2
This setpoint adjusts the delay after engine start when the alarms configured as
RunOnlyBlkDel2 (i.e. "running only", group #2) are started to be evaluated. The
"running only" alarms are not beeing evaluated while the engine is not running or
then, after start, while the adjusted delay is running.
See the setpoint RunOnlyBlkDel1 for diagram of alarm groups and their blocking
periods.
Setpoint: RunOnlyBlkDel3
This setpoint adjusts the delay after engine start when the alarms configured as
RunOnlyBlkDel3 (i.e. "running only", group #3) are started to be evaluated. The
"running only" alarms are not beeing evaluated while the engine is not running or
then, after start, while the adjusted delay is running.
See the setpoint RunOnlyBlkDel1 for diagram of alarm groups and their blocking
periods.