EasyManuals Logo

ComAp IS-NTC-BB Reference Guide

ComAp IS-NTC-BB
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #194 background imageLoading...
Page #194 background image
IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
194
Setpoint: GCB open level
Group
Sync/Load Cont
Range [units]
0 .. 100 [%]
Related FW
3.0
Description
This setpoint adjusts the end point of the gen-set unloading ramp, i.e. power level
at which the GCB is opened. If this level is not reached within time period adjusted
by setpoint GCB open del the GCB is then opened regardless of the gen-set
power.
NOTE:
The speed of the ramp is adjusted by the setpoint Load ramp.
Setpoint: GCB open del
Group
Sync/Load Ctrl
Range [units]
Load ramp .. 1800 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the maximum duration of the gen-set unloading ramp. If the
end point of the ramp (GCB open level) is not reached within time period adjusted
by this setpoint the GCB is then opened regardless of the gen-set power.
NOTE:
The speed of the ramp is adjusted by the setpoint Load ramp.
Setpoint: Sync timeout
Group
Sync/Load Ctrl
Range [units]
1 .. 1800, NO TIMEOUT [s]
Related FW
3.0
Description
This setpoint adjusts the maximum duration of forward or reverse synchronization.

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals