EasyManua.ls Logo

ComAp IS-NTC-BB

ComAp IS-NTC-BB
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
20
Gen1
Priority 1
Gen2
Priority 2
Gen3
Priority 3
Gen 1 = Running, Loaded
Gen 2
#LdResStrt1
#LdResStrt1
#NextStrt del
Running
Gen 3
#NextStrt del
Running
#LdResStp1
#NextStp del
Unloading / Cooling
#NextStp del
Unloading / Cooling
#LdResStp1
Actual power [ kW or kVA ]
Time
BO Syst res OK
#LdResStrt1
Relative power management in %
Guarantees that the engines are not continuously loaded more than to a certain level. Suitable for engine
life-based optimization.
Activation: Pwr management:#Pwr mgmt mode = REL (%)
Figure: Power management function in absolute mode

Table of Contents

Other manuals for ComAp IS-NTC-BB

Related product manuals