IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
21
Gen1
Priority 1
Gen2
Priority 2
Gen3
Priority 3
Gen 1 = Running, Loaded
Gen 2
#%LdResStrt1
= 25%
#%LdResStrt1
= 25%
#NextStrt del
Running
Gen 3
#NextStrt del
Running
#%LdResStp1
=37%
#NextStp del
Unloading / Cooling
#NextStp del
Unloading / Cooling
#%LdResStp1
=37%
Actual power [ kW or kVA ]
Time
BO Syst res OK
#%LdResStrt1
= 25%
St
art/Stop conditions in Power management
Reserve
Actual Reserve
Start condition
Stop condition
Absolute
kW / kVA
ARstrt = ΣPg
Nom
ΣPg
Act
ARstp = ΣPg*
Nom
ΣPg
Act
ARstrt < #LdResStrt
ARstp > #LdResStp
Relative
%
RRstrt = [(ΣPg
Nom
ΣPg
Act
) / ΣPg
Nom
].100%
RRstp = [Pg*
Nom
ΣPg
Act
) / ΣPg*
Nom
].100%
RRstrt < #%LdResStrt
RRstp > #%LdResStp
Where
ARstrt
Actual Absolute reserve in kW or kVA - for engine start calculation.
ARstp
Actual Absolute reserves in kW or kVA - for engine stop calculation.
RRstrt
Actual Relative reserve in % - for engine start calculation.
RRstp
Actual Relative reserves in % - for engine stop calculation.
ΣPg
Nom
Sum of Nominal power of all gen-sets on the bus.
Figure: Power management function in relative mode

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals