IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
208
ExtValue 3 is never lowered below this limit.
NOTE:
This limit is not taken into account if the value ExtValue 3 is written remotely from
a terminal using the appropriate command ExtValue #n.
NOTE:
For IS-NT only.
Setpoint: ExtValue3HiLim
Group
Force value
Range [units]
ExtValue3LoLim .. 32000 [X]
Related FW
3.0
Description
This setpoint adjusts the high limit of the value of ExtValue 3 if the value is
lowered/raised by the binary inputs ExtValue3 up and ExtValue3 down. The
ExtValue 3 is never raised over this limit.
NOTE:
This limit is not taken into account if the value ExtValue 3 is written remotely from
a terminal using the appropriate command ExtValue #n.
NOTE:
For IS-NT only.
Setpoint: ExtValue3 rate
Group
Force value
Range [units]
1 .. 10000 [X/s]
Related FW
3.0
Force value
possible
YES
Force value
possible
YES
Description
This setpoint adjusts the rate pre second at which the ExtValue 3 is beeing
changed while the input ExtValue3 up or ExtValue3 down is active.
Setpoint: ExtValue4deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
3.0
Force value
possible
YES
Force value
possible
YES
Description
This setpoint adjusts the reset (initial) value of the ExtValue 4. This initial value is
applied either when the controller is powered-on or when the ExtValue 4 is reset

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals