IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
While this input is active the value of ExtValue 2 is contiously beeing increased at
the rate of ExtValue2 rate until it reaches ExtValue2HiLim.
NOTE:
If this input is used (configured), the ExtValue 2 can't be written remotely from a
remote terminal using the command ExtValue 2.
Binary input: ExtValue2 down
IS-NT specific function
While this input is active the value of ExtValue 2 is contiously beeing decreased at
the rate of ExtValue2 rate until it reaches ExtValue2LoLim.
NOTE:
If this input is used (configured), the ExtValue 2 can't be written remotely from a
remote terminal using the command ExtValue 2.
Binary input: ExtValue3 up
For IS-NT only.
While this input is active the value of ExtValue 3 is contiously beeing increased at
the rate of ExtValue3 rate until it reaches ExtValue3HiLim.
NOTE:
If this input is used (configured), the ExtValue 3 can't be written remotely from a
remote terminal using the command ExtValue 3.
Binary input: ExtValue3 down
IS-NT specific function
While this input is active the value of ExtValue 3 is contiously beeing decreased at
the rate of ExtValue3 rate until it reaches ExtValue3LoLim.
NOTE:
If this input is used (configured), the ExtValue 3 can't be written remotely from a
remote terminal using the command ExtValue 3.
Binary input: ExtValue4 up
For IS-NT only.
While this input is active the value of ExtValue 4 is contiously beeing increased at
the rate of ExtValue4 rate until it reaches ExtValue4HiLim.
NOTE:
If this input is used (configured), the ExtValue 4 can't be written remotely from a