IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
237
by the optimalization function.
Value: Act Reserve
Group
Pwr management
Units
-
Related FW
3.0
Description
Actual absolute reserve.
Value: Reserve
Group
Pwr management
Units
-
Related FW
3.0
Description
Actual absolute reserve for start. This value contains a copy of the setpoint
#LoadResStrt from the currently selected reserve set.
Value: Reserve Stp
Group
Pwr management
Units
kX
Related FW
3.0
Description
Actual absolute reserve - when the reserve is higher than this value the last
started gen-set (the gen-set with the highest priority) is stopped. This value
contains the following: #LoadResStop plus Nominal power of the genset which is
first to stop. #LoadResStop is used from the currently selected reserve set.
Value: ActRes rel
Group
Power management
Units
%
Related FW
3.0
Description
Actual relative reserve.
Value: Res rel
Group
Power management
Units
%
Related FW
3.0
Description
Actual relative reserve for start. This value contains a copy of the setpoint
#%LdResStrt from the currently selected reserve set.
Value: ResStp rel
Group
Power management

Table of Contents