IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
Bits of this value show "1" if the controller which has address corresponding with
the bit position plays active role in the power management. Bit 0 represents
address 1 etc. This value contains information about controllers with addresses 1-
16.
Value: Reg32
Bits of this value show "1" if the controller which has address corresponding with
the bit position plays active role in the power management. Bit 0 represents
address 17 etc. This value contains information about controllers with addresses
17-32.
Value: GL16
Bits of this value show "1" if the controller which has address corresponding with
the bit position has GCB closed. Bit 0 represents address 1 etc. This value
contains information about controllers with addresses 1-16.
Value: GL32
Bits of this value show "1" if the controller which has address corresponding with
the bit position has GCB closed. Bit 0 represents address 1 etc. This value
contains information about controllers with addresses 17-32.
Value: Combi select
This value indicates which application is currently selected in Combi application.
Value: Engine state
Code of the current state of the engine control. The text representation of each
code can be obtained following way: