EasyManua.ls Logo

ComAp IS-NTC-BB

ComAp IS-NTC-BB
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
314
ALARM STATES AND BEHAVIOR OF RELATED OUTPUTS
Binary output: Horn
Related FW
3.0
Description
The output closes together with the output Alarm. It opens when the output Alarm
is opened or Horn reset button is pressed or Horn timeout has elapsed.
Binary output: CommonAlLev 1
Related FW
3.0
Description
This output is active if there is at least one unconfirmed 1st-level (yellow) alarm
present in the alarm list. See the chapter Alarm management for more
information.
Binary output: CommonAlLev 2
Related FW
3.0
Description
This output is active if there is at least one unconfirmed 2nd-level (red) alarm
present in the alarm list. See the chapter Alarm management for more

Table of Contents