IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
of this output is to be selected by the setpoint Fuel solenoid.
NOTE:
Learn more in the separate chapter Starting sequence.
Binary output: Prestart
This output can be used for control of any device, which has to be activated just
before start, i.e. glow plugs. The output is closed for time period of Prestart time
prior to activating of the starter motor and remains closed during cranking and
also during pause between cranking attempts.
NOTE:
Learn more in the separate chapter Starting sequence.
Binary output: Alarm
The output is closed if there is at least one unconfirmed alarm in the alarm list.
NOTE:
Some alarm types as e.g. Off load, History record, Low power, Mains protection do
not require confirmation, they disappear from the alarm list automatically when the
alarm condition disappears. That means the Alarm output is not activated by
alarms of these types.