IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
This setpoint adjusts "firing" speed level. When this level is reached during
cranking, the engine is considered as started and the starter motor is disengaged,
i.e. the output Starter is deactivated.
NOTE:
There are also other symptoms that causes disengagement of the starter. See the
separate chapter Starting sequence.
This setpoint is also used as the speed limit for the Underspeed protection, which
is activated 5s after the starter was disengaged and the controller continued from
Starting to Idle or Running phase.
Setpoint: Starting POil
Oil pressure can be used as one of the symptoms that are used for detection that
the engine is running. This setpoint adjusts oil pressure limit above which the
engine is considered as started.
NOTE:
Learn more in the separate chapter Starting sequence.
NOTE:
The logical analog input Oil pressure must be configured onto the apporpriate
analog input where the oil pressure sensor is connected.
Setpoint: Prestart time
This setpoint adjust length of the prestart period before starter is engaged. The
output Prestart is active during the prestart period. Adjust the setpoint to zero if
you want to disable the prestart function.
Setpoint: Prelubr time