IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
324
Description
This IS-NT specific function!
The output is closed while there is at least one alarm of the Low power type
present in the alarm list. See the chapter Alarm management for more
information.
Binary output: Common OfL
Related FW
3.0
Description
The output is closed while there is at least one alarm of the Off load type present
in the alarm list. See the chapter Alarm management for more information.
Binary output: Common BOC
Related FW
3.0
Description
The output is closed while there is at least one alarm of the Breaker open&Cool-
down type present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter Alarm
management for more information.
Binary output: Common MP
Related FW
3.0
Description
The output is closed while there is at least one alarm of the Mains protection type
present in the alarm list. See the chapter Alarm management for more
information.
Binary output: Common Al
Related FW
3.0
Description
The output is closed while there is at least one alarm of the Alarm only type
present in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed. See the chapter Alarm management for
more information.
Binary output: Common Hst
Related FW
3.0
Description
The output is closed for 1s when any alarm of History record type appears. See
the chapter Alarm management for more information.
Binary output: CommonActLev 1
Related FW
3.0
Description
The output is closed while there is at least one 1st level (yellow) alarm present in
the alarm list. The alarm can be in any state, i.e. active unconfirmed, active
confirmed or inactive unconfirmed. See the chapter Alarm management for more
information.

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals