Binary output: Ready
The output is closed while the gen-set is not in operation at the moment, however
it is ready to be put into operation. The output is closed while:
ï‚· the genset is not running and
ï‚· the controller is not in OFF mode and
ï‚· there isn't any alarm blocking start of the gen-set
Binary output: Not ready
The output is closed while the gen-set is not in operation, however it is not ready
to be put into operation. The output is closed while:
ï‚· the genset is not running and
ï‚· the controller is in OFF mode or
ï‚· there is an alarm blocking start of the gen-set.
Binary output: CrankProcedure
The output is closed while the engine is cranking and during pauses between
crank attemps. The output is opened either when the gen-set is started or failed to
start. See the diagram in the descrition of the output Cranking for differencies
between outputs CrankProcedure, Cranking and Starter.
Binary output: Starting
The output is closed at the beginning of the prestart phase and remains closed
during prestart, cranking and starting phases. The output is opened either when
the gen-set goes to running phase or when it failed to start. See the diagram in the
descrition of the output Cranking for details.
Binary output: Idle run
This output is closed while the timer Idle time is counting down. This timer begins
to count down when the engine is considered as started and the starter motor is
deenergized. See also description of the output Starter.