IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
351
See also the output ROCOF Trp.
Binary output: ROCOF Trp
Related FW
3.0
Description
The output closes if the ROCOF protection gets active and the controller trips the
selected breaker. The output stays closed for 3s, then opens again.
NOTE:
See also the output ROCOF Act.
Binary output: RemoteControl1
Related FW
3.0
Description
This is a general purpose output, which can be closed and opened remotely, e.g.
from InteliMonitor using the "Remote switches" tool or via MODBUS using the
register #46361 and command #26.
NOTE:
See the Remote switches chapter in the InteliMonitor help for details about how to
control the output from InteliMonitor and the Modbus chapter in the latest
communication guide for information about control the output using Modbus.
Binary output: RemoteControl2
Related FW
3.0
Description
This is a general purpose output, which can be closed and opened remotely, e.g.
from InteliMonitor using the "Remote switches" tool or via MODBUS using the
register #46361 and command #26.
NOTE:
See the Remote switches chapter in the InteliMonitor help for details about how to
control the output from InteliMonitor and the Modbus chapter in the latest
communication guide for information about control the output using Modbus.
Binary output: RemoteControl3
Related FW
3.0
Description
This is a general purpose output, which can be closed and opened remotely, e.g.
from InteliMonitor using the "Remote switches" tool or via MODBUS using the
register #46361 and command #26.
NOTE:
See the Remote switches chapter in the InteliMonitor help for details about how to
control the output from InteliMonitor and the Modbus chapter in the latest
communication guide for information about control the output using Modbus.
Binary output: RemoteControl4
Related FW
3.0
Description
This is a general purpose output, which can be closed and opened remotely, e.g.
from InteliMonitor using the "Remote switches" tool or via MODBUS using the

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals