EasyManuals Logo

ComAp IS-NTC-BB Reference Guide

ComAp IS-NTC-BB
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #355 background imageLoading...
Page #355 background image
IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
355
Description
This output is closed while the Overspeed alarm is present in the alarm list.
Alarm output: Underspeed
Related FW
3.0
Description
This output is closed while the Underspeed alarm is present in the alarm list.
Alarm output: Start fail
Related FW
3.0
Description
This output is closed while the Start fail alarm is present in the alarm list. See the
diagram in the description of the Starter output for information when the start fail
alarm is indicated.
Alarm output: Sd Stop fail
Related FW
3.0
Description
This output is closed while the Sd Stop fail alarm is present in the alarm list. This
alarm appears when the gen-set indicates that it is rotating although it has to be
stopped. This situation can occur:
ï‚· when the gen-set starts to rotate spontaneously (from the controller point
of view) or
ï‚· when the gen-set does not stop after the stop command has been issued.
See the timing diagram in the description of the output Stop Solenoid.
Alarm output: ChrgAlternFail
Related FW
3.0
Description
This output is closed while the ChrgAlternFail alarm is present in the alarm list.
This alarm appears when the voltage at the controller D+ terminal drops below
90% of the controller supply voltage for more than 2s.
NOTE:
Function of the D+ terminal is selected by the setpoint D+ Function.
Alarm output: Pickup fail
Related FW
3.0
Description
This output is closed while the ChrgAlternFail alarm is present in the alarm list.
This alarm appears when the engine is running (there is at least one "running
symptom" active), however zero speed is detected.
NOTE:
Pickup fail can be indicated even if the speed is actually measured from the
generator frequency.
The "running symptoms" are listed in the description of the output Starter.

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals