IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
Alarm output: WrongConfig
This output is closed while there is the WrongConfig alarm present in the alarm
list. The wrong configuration is indicated if the controller configuration contains a
PLC program, which exceeds limits of the current controller hardware. Typically
this situation can occur when a miniCHP archive is used in a controller without
mCHP dongle inserted.
Alarm output: Dongle incomp
This output is closed while there is the Dongle incomp alarm present in the alarm
list. The incompatible dongle is indicated when a function is switched on, which
requires dongle, however the dongle is not inserted or does not contain the
appropriate feature.
Typical situations are:
ï‚· Power management is enabled and there is not any dongle with "PMS"
feature inserted in the controller.
ï‚· The controller is in situation, when the load sharing should beeing
performed, however there is not any dongle with "LS" feature inserted in
the controller.
Alarm output: Emergency stop
This output is closed while the Emergency stop alarm is present in the alarm list.
The emergency stop alarm is activated by the input Emergency stop.
Alarm output: WrnServiceT1+2
This output is closed while the WrnServiceT1+2 alarm is present in the alarm list.
This alarm occurs when the counter Service time 1 or Service time 2 has reached
zero value. Both timers must be reset to a nonzero value to get rid of this alarm.
Alarm output: WrnServiceT3+4
This output is closed while the WrnServiceT3+4 alarm is present in the alarm list.
This alarm occurs when the counter Service time 3 or Service time 4 has reached
zero value. Both timers must be reset to a nonzero value to get rid of this alarm.
Alarm output: Overspeed