62
Default protections in Combi
Fix – firmware based protections
ENGINE
PROTECTION TYPE
CORESPONDING SETPOINTS
Overspeed
SD
Engine protections: Overspeed
Underspeed
SD
Engine params: Starting RPM
GENERATOR
PROTECTION TYPE
CORESPONDING SETPOINTS
IDMT overcurrent
BOC
Basic settings: Nomin current; Gener
protect: 2Inom del
IDMT Active power
BOC
Gener protect: OverldStrtEval;
2POvrldStrtEvDel
IDMT EarthFault Current
BOC
Gener protect: NomEthFltCurr,
2EthFltCurr del
Shortcurrent
BOC
Gener protect: Ishort; Ishort del
Generator voltage: Ug1>, Ug1<, Ug2>,
Ug2<, Ug3>, Ug3<
BOC
Gener protect: Gen >V BOC; Gen <V
BOC; Gen V del.
Generator voltage: Ug1>>, Ug2>>, Ug3>>
Sd
Gener protect: Gen >V Sd; Gen V del.
Generator frequency: fg<, fg>
BOC
Gener protect: Gen >f; Gen <f; Gen V
del
Excitation Loss
BOC
Gener protect: ExcitationLoss,
ExctLoss del
MAINS
PROTECTION TYPE
CORESPONDING SETPOINTS

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals