Reviewing Day Statistics on the Display VFC400-WiFi User Guide 39
Data from 6 days ago
After pressing the button for a few times (skipping days -3
to -5) the maximum statistic from six days ago is displayed:
l
The
flashes to indicate that the data being displayed
are from seven days ago.
l Six days ago recordings above the upper threshold were
recorded, indicated by the upper alarm threshold marker.
l The duration was 6 hour 30 minutes, which was shorter
than the allowed period, so no alarm event was
generated.
l The maximum temperature recorded six days ago was
10.5°C.
Data from 7 days ago
After pressing the button twice (skipping the minimum
statistics for day -6) the maximum statistic from seven days
ago is displayed:
l
The
flashes to indicate that the data being displayed
are from seven days ago.
l Seven days ago recordings above the upper threshold
were recorded, indicated by the upper alarm threshold
marker.
l The duration was 5 hour 30 minutes.
l An alarm event was generated
. Neither duration from
day -6 nor -7 by itself would cause an alarm event,
however the combined duration is 10 hours 50 minutes,
which is more than the allowed 10 accumulative hours.
l The maximum temperature recorded eight days ago
was 11.5°C.
Tip: Pressing and holding the button will get you back to the previous screen, rather than
advancing one screen.

Related product manuals