Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Options Parameter List
UL Listing
Information
Commander SK Size 2 to 6 Getting Started Guide 13
Issue Number: 2 www.controltechniques.com
Table 2-14 Commander SK5, 690V drive, 3 phase, 500 to 690VAC ±10%, 48 to 65Hz units
Table 2-15 Commander SK6, 400V drive, 3 phase, 380 to 480VAC ±10%, 48 to 65Hz units
Table 2-16 Commander SK6, 575V drive, 3 phase, 500 to 575VAC ±10%, 48 to 65Hz units
Table 2-17 Commander SK6, 690V drive, 3 phase, 500 to 690VAC ±10%, 48 to 65Hz units
* These are Normal Duty values.
** Semi conductor fuse in series with HRC fuse or circuit breaker.
Model
number
Normal Duty Heavy Duty
Typical
full load
input
current*
Maximum
continuous
input
current*
Fuse option 1 Fuse option 2**
Minimum
braking
resistor
value
Instantaneous
power rating
Nominal
motor
power
100%
RMS
output
current
Nominal
motor
power
100%
RMS
output
current
150%
overload
current
for 60s
European
input fuse
rating
IEC gR
USA Input
fuse
rating
Ferraz
HSJ
HRC
IEC class
gG
UL class
J
Semi-
conductor
IEC class
aR
kW hp A kW hp A A A A A A A A
Ω
kW
SK5601 75 100 84 55 75 63 93 75.5 82.6
125 100
90
160 10 125.4
SK5602
90 125 99 75 100 85 126 89.1 94.8 125
Model
number
Normal Duty Heavy Duty
Typical
full load
input
current*
Maximum
continuous
input
current*
Fuse option 1 Fuse option 2**
Minimum
braking
resistor
value
Instantaneous
power rating
Nominal
motor
power
100%
RMS
output
current
Nominal
motor
power
100%
RMS
output
current
150%
overload
current
for 60s
European
input fuse
rating
IEC gR
USA Input
fuse
rating
Ferraz
HSJ
HRC
IEC class
gG
UL class
J
Semi-
conductor
IEC class
aR
kW hp A kW hp A A A A A A A A
Ω
kW
SK6401 110 150 205 90 150 180 231 206 215 250 250 250 315
5 121.7
SK6402 132 200 236 110 150 210 270 247 258 315 300 300 350
Model
number
Normal Duty Heavy Duty
Typical
full load
input
current*
Maximum
continuous
input
current*
Fuse option 1 Fuse option 2**
Minimum
braking
resistor
value
Instantaneous
power rating
Nominal
motor
power
100%
RMS
output
current
Nominal
motor
power
100%
RMS
output
current
150%
overload
current
for 60s
European
input fuse
rating
IEC gR
USA Input
fuse
rating
Ferraz
HSJ
HRC
IEC class
gG
UL class
J
Semi-
conductor
IEC class
aR
kW hp A kW hp A A A A A A A A
Ω
kW
SK6601 90 125 125 75 100 100 128 128 139
160 175
150
315
SK6602 110 150 144 90 125 125 160 144 155 160
Model
number
Normal Duty Heavy Duty
Typical
full load
input
current*
Maximum
continuous
input
current*
Fuse option 1 Fuse option 2**
Minimum
braking
resistor
value
Instantaneous
power rating
Nominal
motor
power
100%
RMS
output
current
Nominal
motor
power
100%
RMS
output
current
150%
overload
current
for 60s
European
input fuse
rating
IEC gR
USA Input
fuse
rating
Ferraz
HSJ
HRC
IEC class
gG
UL class
J
Semi-
conductor
IEC class
aR
kW hp A kW hp A A A A A A A A
Ω
kW
SK6601 110 150 125 90 125 100 128 128 139
160 175
150
315
SK6602 132 175 144 110 150 125 160 144 155 160