Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Menu 0
Running
the motor
Optimisation Macros
Advanced
Parameters
Technical
Data
Diagnostics
UL Listing
Information
Unidrive User Guide 69
Issue Number: 9 www.controltechniques.com
Types of current range
FLC Full load current of the drive (maximum continuous output
current up to 40
o
C ambient temperature). Displayed in Pr 11.32
{0.22}.
I
MAX
A Maximum overload output current of the drive up to 40
o
C
ambient temperature, derived as follows:
120% x FLC
I
MAX
% See section 8.2 Current limits on page 98 for the definition of
I
MAX
%.
Where a parameter is represented by a text value, the value in brackets
in the range column is the setting used for serial communications.
P
MAX
3I
MAX
×
Pr5.09
1000
------------------
×=
NOTE