NOTES:
1. When used in a single-transformer system, leave metal jumper wire in place between RC and
R. If used on a two-transformer system, remove metal jumper wire between RC and R.
2. Common wire is optional when thermostat is used with batteries.
3. If thermostat is configured for a heat pump system in the Installer Setup, configure
changeover valve for cool (O-factory setting) or heat (B).
4. L terminal is an input (system monitor) when the System mode is in the HEAT, OFF, COOL or
AUTO position. “L” terminal is a 24VAC output when System mode is Emergency Heat. When
using the “L” terminal connect the 24VAC Common. See LCD indications on page 90.
.