4 Modbus/TCP
Ethernet Option Board /
700.002 735 AE01
4-9
4.6.3 Energy Counter 30201 – 30203
The last number of the 'Format' field indicates the decimal point place in the 'Energy' field.
If the number is bigger than 0, move the decimal point to the left by the number indicated. For example,
Energy = 1200, Format = 52. Unit = 1. Energy = 12.00kWh
Address Purpose
30201 Energy
30202 Format
30203 1 = kWh
2 = MWh
3 = GWh
4 = TWh
Table 4-19: Energy Counter
4.6.4 Reset table Energy Counter 30301 – 30303
Address Purpose
30301 Energy
30302 Format
30303 1 = kWh
2 = MWh
3 = GWh
4 = TWh
Table 4-20: Reset table Energy Counter
4.6.5 Error History 30401 – 30417
The error history can be viewed by reading from the address 30401 onward. The errors are listed in
chronological order so that the latest error is mentioned first and the oldest is mentioned last. The error history
can contain 16 errors at any time. The error history contents are represented as follows.
Error code Sub-code
Value as a hexadecimal Value as a hexadecimal
Table 4-21: Error Coding
For example, the IGBT temperature error code 41, sub-code 00: 2900Hex -> 4100Dec. For complete list of
error codes please see frequency converter’s manual