5 Start up Test
Ethernet Option Board /
700.002 735 AE01
5-1
5 Start-up Test
Once the option board has been installed and configured, its operation can be verified by writing a frequency
instruction and giving a run command to the frequency converter via fieldbus.
5.1 Frequency Converter Settings
Select fieldbus as the active control bus. (For more information see the Converteam LV7000 Operating
Manual, section 7.3.3).
5.2 Master Unit Programming
Write a FB 'Control Word' (address: 42001) of value 1Hex
The frequency converter is now in the RUN mode.
Set the FB 'Speed Reference' (address: 42003) value of 5000 (= 50.00%).
The engine is now running at a 50% speed.
Write a 'FB Control Word' (address: 42001) value of 0Hex'
Following this, the engine stops.