Technical SpecificationTechnical Specification
Power Specification
Mains Fuse : 1.6A Slow Blow
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
The Panel is protected by an internal thermal device, this requires no maintenance
Batteries
Number of Batteries : 2
Manufacturer: :YSP12-7
Capacity : 7 Ah
Battery Fuse : 4A Quick Blow (F4)
Maximum battery current; : 3.5 Amps
Standby current (mA) : 100 (1 loop )
Inputs
Addressable Loops
Max Number : 1 or 2 (Panel depending)
Max Loop Load per loop : 500 mA
Max Number of Addressable Devices per loop : 150
Class Change : Operated by external volt free
contact
Outputs
Conventional sounder circuits
Number of sounder circuits : 2
Total sounder Load : 1.5 Amps
Sounder Circuit Fuses (F1/2/3/4) : 1.6 Amp (Quick Blow)
End of line resistor : 6k8
Fire Routing Equipment
Max Load : 60 mA
Fused (PTC2) : 100mA polyswitch
End of Line resistor : 6k8
Fire Protecting Equipment
Max Load : 60 mA
Fused (PTC3) : 100mA polyswitch
End of Line resistor : 6k8
Fault Routing equipment
Max Load : <10 mA
Fused (PTC1) : 100mA polyswitch
End of Line resistor : 6k8
Auxiliary Relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not
monitored.
Max Load : 24 Volts 1 Amp
Fuse (PTC4) : 1.35 Amps polyswitch
Power Specification
Batteries
Inputs
Outputs
Mains Fuse : 1.6A Slow Blow
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
The Panel is protected by an internal thermal device, this requires no maintenance
Number of Batteries : 2
Manufacturer: :YSP12-7
Capacity : 7 Ah
Battery Fuse : 4A Quick Blow (F4)
Maximum battery current; : 3.5 Amps
Standby current (mA) : 100 (1 loop )
Addressable Loops
Max Number : 1 or 2 (Panel depending)
Max Loop Load per loop : 500 mA
Max Number of Addressable Devices per loop : 150
Class Change : Operated by external volt free
contact
Number of sounder circuits : 2
Total sounder Load : 1.5 Amps
Sounder Circuit Fuses (F1/2/3/4) : 1.6 Amp (Quick Blow)
End of line resistor : 6k8
Max Load : 60 mA
Fused (PTC2) : 100mA polyswitch
End of Line resistor : 6k8
Max Load : 60 mA
Fused (PTC3) : 100mA polyswitch
End of Line resistor : 6k8
Max Load : <10 mA
Fused (PTC1) : 100mA polyswitch
End of Line resistor : 6k8
The auxiliary relays provide fused volt free change over contacts. These contacts are not
monitored.
Max Load : 24 Volts 1 Amp
Fuse (PTC4) : 1.35 Amps polyswitch
Conventional sounder circuits
Fire Routing Equipment
Fire Protecting Equipment
Fault Routing equipment
Auxiliary Relays