Standard Recommended Procedure 003-794-AEN | Issue 14 | March 2020 | Page 3 of 27
4. Installation
4.1 Rack or Frame Mounting
Step 1: Identify the position on the rack where the housing will be installed and partially install screws to rest
the mounting brackets on Figure 2.
Step 2: Move brackets forwards or backwards for desired frontal projection and rest the mounting brackets
behind the screw heads just installed in the rack.
Step 3: Install screws into the rack through the mounting brackets.
Step 4: If installing a 2U or 4U housing, slide the ber management ngers onto the housing.
NOTE: Installation of ber management ngers is essential to ensure proper jumper management.
4.2 Install Trunk Cables
The EDGE™ Trunk Cable is supplied with factory-installed protection/pulling grips (Figure 3) to protect the
connectors and their bers by coupling the pulling load back to the cable. The cradle is used to install the
furcation plug into the housing.
Figure 2 — Rack or Frame Mounting
Figure 3 — Cable with Pulling Grips