Step 5: Documentation (Figure 30)
Identify remote location termination and determine code to be printed. It should only be necessary
to print the remote location. Printed code from label makers may be axed to the label card on the
inside of the front door.
Figure 30 — Print Remote Termination Label
5.2 Cable/Jumper Labeling
Fiber termination identication is equally important in mapping the data center network. Individual bers
(such as jumpers) must be clearly labeled to identify local and remote location. Typically a single jumper will
contain two labels on each end of the ber near the termination point identifying the specic local id and the
remote id the jumper is patching to. It is important to follow suite with previous dened code indicating rack
or cabinet id, patch panel id and more specically the individual port or ber termination location. One should
cross reference the recommended guidelines in ANSI/TIA-606-A-1. Proper labeling allows users to easily trace
jumpers from one location within the network to the next.
Most common identication methods for individual ber id employ the use of ag or wrap around preprinted
labels. Barrel or snap-on labels may also be employed but user must select the proper barrel label for the
corresponding jumper diameter, e.g., 2.0 mm. Documentation should clearly identify individual ber strands of
the cable or jumper.