94
collector blocked
A collector is considered to be blocked, if either the
sensor is defective or the emergency shutdown tem-
perature is reached.
Pump speed is controlled according to collector tem-
perature rather than (usual) temperature difference.
The aim is to maintain constant collector temperature,
adjustable with parameter “Tcolset“.
Target temperature:
Solar/Options/Target tem.
selection „Yes“, „No“
factory setting: „No“
if you select „Yes“.
Solar/adj. values/tcolset
adjustment range: 20 ... 110 °C
factory setting: 65 °C
Parallel relay:
Solar/Options/Par. Relay
selection: „Yes“, „No“
factory setting: „No“
If the solar circuit pump is switched on, this relay is
activated in parallel.
In 2-collector systems which are working with 2 pumps,
the parallel relay is activated if one of the 2 pumps is
activated.
CS-Bypass:
Solar/Options/CS-Bypass
selection: „Yes“, „No“
factory: setting „No“
if you select „Yes“:
Solar/adj. values/CS-Byp.
adjustment range: 100 ... 500 W/m
2
factory setting: 200 W/m
2
If the irradiation exceeds the adjusted value CS-bypass,
the collector circuit is operated. It is switched off when
the irradiation has fallen below the value „CS-bypass“
for at least 2 minutes.
The collector circuit is operated with minimum pump
speed.
2-collector systems:
If a loading of the store is carried out in these systems,
the function is switched off.
Collector emergency shutdown:
Solar/adj. values/Tcolsec
adjustment range: 110 ... 200 °C
factory setting: 120 °C
hysteresis: 10 K
At high collector temperatures (depending on system
pressure or antifreeze concentration etc.) the systems
stagnates. This means that solar loading is not possible.
If the adjusted temperature threshold „Tcolsec“ is ex-
ceeded, the corresponding collector will no longer be
used for loading.
Afterheating suppression:
Solar/Options/ah suppress.
selection: „Yes“, „No“
factory setting: „No“
if you select „Yes“:
Solar/Expert/ah suppress.
adjustment range: St 1 ... St 4
factory setting: St 1
This function is active if a previously selected solar
store (parameter designation: “AH suppress.“ in the
menu solar expert) is being loaded.
Solar loading means that store loading is only carried
out for energy supply and not for cooling purposes etc.
4. Functions and options