Program Menu Notes
1
rottle types (see rottle Wiring in Section 2)
Type 0: 0–5kΩ, 2-wire pot
Type 1: 5kΩ–0, 2-wire pot
Type 2: single-ended 0–5V input
Type 3: single-ended 3-wire pot (1–10kΩ)
2
Lift lockout types (see Section 3: Programmable Parameters, page 25)
Type 0: Enable = low; Disable = high or open
Type 1: Enable = high or open; Disable = low
Type 2: Enable = high; Disable = low or open
Type 3: Enable = low or open; Disable = high
3
Precharge function and fault detection depend on the combined
setting of two parameters, Precharge and Contactor Control
(see Section 3: Programmable Parameters, pages 28, 27)
Parameter Setting
Precharge Precharge Fault
PRECHARGE CONTACT CNTRL Performed Detection
ON off YES YES
ON ON YES YES
off off YES no
off ON no no
4
Startup lockout types (see Section 3: Programmable Parameters, page 26)
Type 0: no startup lockout
Type 1: startup lockout unless KSI input is received before speed request
Type 2: startup lockout unless KSI and interlock inputs are both received
before speed request
APPENDIX B: PROGRAMMING DEVICES & MENUS