= [200V] [208V] [220V] [230V] [240V]
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
[Check Freq/Volt] [Check Volt Only] [No Bypass]
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
[English] [Español-Spanish] [Français-French] [Deutsch-German]
[I/P Power Fail] [Battery Low] [Summary Alarm] [UPS On Bypass] [UPS Fail]
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
[Disable] [1 Minutes] [5 Minutes]
*) 200V are derated by 20%, 208 V are derated by 10% for OL6000RT3U
**) This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
***) UPS has no bypass when Generator Mode is enabled.
****) UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
SILENCING AUDIBLE ALARMS
1. Press any of four function buttons on the LCD module; Note: the alarm can not be turned off for a “Battery Low”
condition. This condition will still result in an audible alarm.
2. Configure “Audible Alarms” as “Disable” on the LCD module and it will stop warning of any malfunction audibly.
MANUAL BATTERY TEST
Configure “Battery Test” as “Active” on the LCD module; and it will perform the “Manual Battery Test”